Voltage scaling
Converts primary voltage to standardized 100 V or 110 V secondary values.
Medium-voltage instrument transformers
PTs convert medium voltage into a standardized, isolated secondary signal so meters, counters, and protection relays can operate safely and accurately.
Measurement and protection
Niroo Trans voltage transformers are available for MV switchgear, substations, metering, and protection, with multiple accuracy classes and indoor or outdoor configurations.
Converts primary voltage to standardized 100 V or 110 V secondary values.
Provides isolated voltage signals for meters, monitoring equipment, and relays.
Technical range
General data for 4VPA, 4VPA1, VPV, and VPV1 voltage-transformer families.
| Characteristic | Symbol | 12 kV | 24 kV | 36 kV |
|---|---|---|---|---|
| Highest system voltage | Um (kV) | 12 | 24 | 36 |
| Insulation level | BIL (kV) | 28–75 | 50–125 | 70–170 |
| Rated primary voltage | Un (kV) | 11, 11/√3 | 20, 20/√3 | 33, 33/√3 |
| Rated secondary voltage | Usn (V) | 100/√3, 110/√3, 100, or 110 V | ||
| Rated secondary burden | VA | Up to 100 VA | ||
| Secondary windings | — | Up to 3 windings | ||
| Accuracy classes | — | 3P, 0.2, 0.5 | ||
| Rated frequency | F (Hz) | 50 / 60 Hz | ||
| Installation | — | Indoor or outdoor | ||